stason.org logo lotus


previous page: 17.0 Typical Wiring Layout (Data Communications Cabling)page up: Data Communications Cabling FAQnext page: 19.0 What is the Minimum Bending Radius for a Cable? (Data Communications Cabling)

18.0 How Far Away Should Cable be Installed from an EMI Source (Data Communications Cabling)

 Books
 TULARC
















Description

This article is from the Data Communications Cabling FAQ, by Peter Macaulay pmac@fox.nstn.ca with numerous contributions by others.

18.0 How Far Away Should Cable be Installed from an EMI Source (Data Communications Cabling)

Northern Telecom IBDN User Manual contains an Appendix D titled
"UTP Separation Guidelines From EMI Sources". The values are the
same as the cabling pathways standard, EIA-569, table 4.8-5.

      Minimum Separation Distance
           from Power Source at 480V or less
     CONDITION                           <2kVA      2-5kVA       >5kVA
     Unshielded power lines or
     electrical equipment in proximity
     to open or non-metal pathways         5 in.     12 in.     24 in.
      (12.7 cm)  (30.5 cm)  (61 cm)
     Unshielded power lines or
     electrical equipment in proximity
     to grounded metal conduit pathway    2.5 in.     6 in.     12 in.
      (6.4 cm)  (15.2 cm)   (30.5 cm)
     Power lines enclosed in a grounded
     metal conduit (or equivalent
     shielding) in proximity
     to grounded metal conduit pathway      -         6 in.     12 in.
         -      (15.2 cm)   (30.5 cm)
  
     Transformers & electric motors       <------- 40-in (1.02 m) ----->
  
     Fluorescent lighting                 <------- 12-in (30.5 cm) ---->

Source: Integrated Building Distribution Network (IBDN) User Manual
- Northern Telecom, doc # IBDN-UM-9105, 1991.

The EIA/TIA working group revising the EIA-569 standard is using the
results of field and lab tests to update the recommendations. The
target date for completion is Dec 1995.

 

Continue to:


Share and Enjoy

Bookmark this story so others can enjoy it:
  • digg
  • Reddit
  • del.icio.us
  • Furl
  • Wists

Tags

networking, cabling, data communications, standards, implementations, 10Base-T, Classification, cable rating, fiber optic cable







TOP
previous page: 17.0 Typical Wiring Layout (Data Communications Cabling)page up: Data Communications Cabling FAQnext page: 19.0 What is the Minimum Bending Radius for a Cable? (Data Communications Cabling)